- Neu
1.092 € Ohne Steuern
BOS-A-PDU-2 is the HV control box of the Deye BOS-A battery cluster. It operates from 200 to 1000 V DC, with a maximum charge and discharge current of 160 A, has two pairs of PCS terminals, a display for state of charge and fault codes, IP20 protection and a weight of 21 kg.
BOS-A-PDU-2 is the high voltage control box of the battery cluster in the Deye BOS-A series. It operates from 200 to 1000 V DC and at charge and discharge currents up to 160 A, has two pairs of PCS terminals and shows the state of charge and fault codes.
The box has a display for the state of charge (SOC) and fault codes, high voltage and alarm indicators, an isolating switch for manually connecting the rack to external devices, a USB port for BMS upgrade and storage expansion, and Bluetooth for connecting the mobile app.
The box communicates with the inverter through the PCS COM port and uses the IN COM and OUT COM ports when several racks are connected in parallel. BOS-A systems can be connected to two DC interfaces of the inverter and can run with up to 16 racks in parallel.
| Type | HV battery cluster control box |
|---|---|
| Operating voltage | 200 ... 1000 V c.c. |
| Maximum charge/discharge current | 160 A |
| DC input rating | 12 V ± 2 %, 4.15 A |
| Operating temperature | -20 ... 65 °C |
| Ingress protection | IP20 |
| Dimensions (W x D x H) | 572 x 632 x 142.2 mm |
| Approximate weight | 21 kg |
Diese technischen Daten wurden von uns aus dem Datenblatt des Herstellers übernommen und können Übertragungsfehler enthalten. Für 100 % Genauigkeit sehen Sie bitte im beigefügten Datenblatt nach.
Die Kompatibilität wird automatisch aus den technischen Daten der Hersteller berechnet und dient nur zur Information. Bei komplexen Anlagen empfehlen wir, die Konfiguration vor der Bestellung von einem Berater prüfen zu lassen. Details in den AGB